Rotor DC Current Measurement by Using Standard Current Transformers

This document was uploaded by one of our users. The uploader already confirmed that they had the permission to publish it. If you are author/publisher or own the copyright of this documents, please report to us by using this DMCA report form.

Simply click on the Download Book button.

Yes, Book downloads on Ebookily are 100% Free.

Sometimes the book is free on Amazon As well, so go ahead and hit "Search on Amazon"

Z. GAJIĆ, ABB SA Products, Sweden
D. TRIŠIĆ, PD Drinsko-Limske HE, Serbia
S. ROXENBORG, ABB SA Products, Sweden
Generator protection has traditionally only measured stator AC currents and voltages. Measurement of rotor DC current was typically more difficult and required special measurement equipment (e.g. resistive shunt) in the rotor DC circuit.
With advance of numerical technology it is now actually feasible for modern Intelligent Electronic Devises (i.e. IEDs) to measure the rotor winding DC current by utilizing standard CTs installed on the excitation transformer which feeds the static exciter (see Figure 1). By utilizing the measured AC currents from this CT the rotor DC current can be accurately measured by the IED. This can improve generator protection in several ways. Also useful information about excitation system behavior can be obtained from such measurements. Theoretical background and actual site measurements in a trail installation on a 315MVA, 11kV synchronous machine in a pump-storage hydro power plant will be presented in this paper.